PROBLEMS OF REACTIVE POWER COMPENSATION OF 110 KV LINE CABLE
DOI:
https://doi.org/10.20319/mijst.2017.32.163172Keywords:
Reactive Power Compensation, HV Cables, Wind Farms, Monte Carlo SimulationAbstract
Construction of 110 kV cable systems, where the line length exceeds ten kilometers requires compensation of reactive power generated by the cable capacitance. The compensation can be realized with the application of shunt reactors, whose selection seems to be an easy task. The presented considerations deal with a problem, whose source are the below listed facts. Both the 110 kV cable and the shunt reactor to be applied are custom made and their quality parameters are subject to random variability, whose source are manufacturing processes. Construction of a cable system and manufacturing of a customized shunt reactor are realized at the same time and hence it is not possible to have the reactor matching the already existing and tested cable line. Taking into account that cable and reactor parameters are of random character, the shunt reactor selection process exhibits features of a stochastic process. The article presents the Monte Carlo simulation results obtained for various parameters of the analyzed HV cable line – shunt reactor system. Various forms of the random variable distribution have been obtained and the random variable is the operation compensation costs. The performed analyses make it possible to select optimal inductance for the shunt reactor. The highest value of the probability that operation costs of the reactive power compensation will not exceed a certain predefined value has been assumed as the selection criterion.
References
Iwanicki M., Dębek M.(2015).Compensation of inductive and capacitive reactive power in wind farms, Wiadomości Elektrotechniczne (Electrotechnical News) No. 2,35-38.
Kacejko P., Pijarski P.(2013).Generation level matching to the transmission capability of overhead lines, Acta Energetica , nr 1/14, vol 5, 43-49.
Kacejko P., Pijarski P.(2009, February).Wind farms connecting - restrictions instead if over-measured investments, Rynek Energii (Energy Market), No. 1 (80),10-15.
Lubośny Z. (2003). Wind turbine operation in electric power systems. Advanced modeling. Springer Verlag, Berlin – Heidelberg – New York.
https://doi.org/10.1007/978-3-662-10944-1
PGE Dystrybucja (2017).(one of the Polish distribution grid operator): tariff of distribution services in 110 kV grid.
Saadat H: (2010). Power System Analysis, McGraw-Hill International Editions, 3-rd edition.
Sobral A., Moura A., Carvalho M., (2011, June).Technical Implementation of Cross Bonding in Underground HV Lines Projects, 21-st International Conference on Electricity Distribution, paper 0499.
Transmission and Operation of Industrial Network Manual PSE SA http://www.pse.pl/.
Downloads
Published
How to Cite
Issue
Section
License
Copyright of Published Articles
Author(s) retain the article copyright and publishing rights without any restrictions.
All published work is licensed under a Creative Commons Attribution-NonCommercial 4.0 International License.